Intrinsically safe products

  • Intrinsically Safe Conventional Rate of Rise and Fixed Temperature Heat Detector

Intrinsically Safe Conventional Rate of Rise and Fixed Temperature Heat Detector

Code: DC-9103(IS)
Manufacturers: GST
Origin: China

Detector Class: P (A1R and BS can be set, factory default is A1R)
Operating Voltage: 16VDC~28VDC
Static Current :≤60μA (Note: In standby state, the detector can work within 16VDC~28VDC)
Alarm Current :10mA≤I≤30mA (Warning: The alarm current depends on the current limit of the FACP. It’s not allowed to power the detector directly by 24VDC. Otherwise the detector will be blown as a result of without current limiting resistor.)
Maximum Ripple Voltage :4V (peak-to-peak)
Alarm Reset: Instantaneous Power-off (5s Min, 2.5VDC Max)
Power-up Time: ≤10s
Alarm Indicator: Red. Flashes in polling. Illuminates when fire is reported.
Explosion-proof Mark :ExibIICT6 Gb
Explosion-proof Certificate No. :CE12.2146
Safety Barrier Parameters: U0=28V, I0=93mA, C0=0.083uF, L0=4mH, Um:250V
Wiring: Polarity-sensitive, two-wire for connecting with power supply
Operating Environment
                      Temperature:
                         A1R: typical temperature is 25℃,ranging -10℃~+50℃
                         BS : typical temperature is 40℃, ranging -10℃~+65℃
                      Relative Humidity: ≤95%, non-condensing
Dimensions Diameter: 100mm Height 53.3mm (with base)
Ingress Protection Rating :IP33
Material and Color of the Enclosure :ABS(surface resistance≤10^9Ω)
Weight About: 130g
Mounting Hole Spacing :45mm~75mm