Hệ thống điều khiển xả khí
Tủ điều khiển xả khí GST301
Conventional Gas Extinguishing Control Panel
• Two plus one control panel
• Standalone gas extinguishing control panel
• 2 conventional detection zones achieve double knock control
• Additional standard fire detection zone for other areas (no effect on gas release)
• Automatic and Manual extinguishing control
• Numerical onboard timer control
• Adjustable gas release delay timer
• Duty and Standby Cylinder control
• Two phase evacuation sounders
• Adjustable Solenoid Pulsed output
• Compatible with all GST conventional detectors
• Fully compliant to BS/EN/CE standards
• Built-in PSU and Charger
Technical Specifications
1 Operating Voltage: 220/230VAC,50/60Hz
2 Power Consumption≤20W (Monitoring Mode)
3 Battery Requirement: 2X12VDC, 7Ah
4 Battery Operating Time:
a) 24 hours monitoring and half an hour alarm if the current of AUX power output is 0mA.
b) 8 hours monitoring and half an hour alarm if the current of AUX power output is 100mA.
5 AUX Power Supply:100mA/24VDC
6 Sounder Output: 0.5A/24VDC
7 Release Output: 2A/24VDC, pulse
8 Battery Charge Current: 300mA
9 Maximum Detectors in Each Zone: 15
10 Maximum Number of C-9317 Emergency Gas Override Control: 4
11 Operating Environment:
Temperature: 0°C~40°C
Relative Humidity: ≤95%, non condensing
12 Dimension: 300mmX350mmX110mm
13 Mounting Hole Distance: 260mm