Interfaces and Zener Barrier
Addressable Explosion Proof Interface for Intrinsically Safe Detectors and MCP
Download Catalogue:
I-9332 (224,07 KB)
|
Operating Voltage |
Loop voltage: 24V Power voltage: 24VDC |
|
Loop Current |
Standby current≤0.5mA Alarm current≤5mA |
|
Address Range |
Occupying one address within 1~ 242 |
|
Ingress Protection Rating |
IP65 |
|
Environmental Temperature |
-10℃~+50℃ |
|
Relative Humidity |
≤95%, non condensing |
|
Dimensions |
201 mm×172 mm×79 mm |
|
Material and Color of Enclosure |
Cast aluminum alloy, silver grey |
|
Weight |
1kg |
|
Mounting Hole Spacing |
155mm or 60mm |
|
Internal safety barrier |
U0=28V, I0=93mA, L0=4mH, C0=0.083F |
|
Wiring |
Connecting with fire alarm control panel and 24VDC power line through polarity-insensitive loop; and with explosion-proof devices through polarity-sensitive loop. |